Basic product symbols: CR6-35kV / 100A
– CR: Falling fuse
– 6 (to 35): nominal voltage (kV)
– 100 (up to 200): nominal current (kV)
The company will meet the type of wire with appropriate current according to customers’ requirements.
The Self-Falling Fuse (CR) is manufactured by EEMC Electric Equipment Design and Construction Limited Company in accordance with IEC Standard 282-2: 1995. These fuses have been previously authorized by the Ministry of Energy. The national electricity grid was approved under Document No. 215 / NL / KHKT dated 21 June 1992 and No. 860NL / KHKT dated 12 May 1993.
SPECIFICATIONS:
DATA | CR6/100 | CR6/100 | CR6/100 | CR6/100 | CR6/100 |
Nominal voltage (kV) | 6,3 | 10 | 15 | 22 | 35 |
Maximum working voltage (kV) | 6,9 | 11,5 | 17,5 | 24 | 40,5 |
The largest nominal line | 100 | 200 | 200 | 200 | 100 |
Industrial frequency test voltage for 1 minute | 32 | 42 | 55 | 65 | 95 |
Pulse-resistant voltage (kVp) | 60 | 75 | 125 | 125 | 170 |
Cutting power (MVA) | 100 | 100 | 200 | 200 | 250 |
Rated asynchronous short circuit (kAm.s) | 5 | 5 | 12 | 12 | 16 |
Maximum environmental temperature (0C) | 45 | 45 | 45 | 45 | 45 |
Maximum relative humidity (%) | 98 | 98 | 98 | 98 | 98 |
Minimum detection line length (mm/kV) | 20 | 20 | 20 | 20 | 20 |
Weight (kg) | 7 | 7 | 8,2 | 8,7 | 13,5 |