The fuse falls on its own

Basic product symbols: CR6-35kV / 100A

– CR: Falling fuse

– 6 (to 35): nominal voltage (kV)

– 100 (up to 200): nominal current (kV)

The company will meet the type of wire with appropriate current according to customers’ requirements.

The Self-Falling Fuse (CR) is manufactured by EEMC Electric Equipment Design and Construction Limited Company in accordance with IEC Standard 282-2: 1995. These fuses have been previously authorized by the Ministry of Energy. The national electricity grid was approved under Document No. 215 / NL / KHKT dated 21 June 1992 and No. 860NL / KHKT dated 12 May 1993.

SPECIFICATIONS:

DATA CR6/100 CR6/100 CR6/100 CR6/100 CR6/100
Nominal voltage (kV) 6,3 10 15 22 35
Maximum working voltage (kV) 6,9 11,5 17,5 24 40,5
The largest nominal line 100 200 200 200 100
Industrial frequency test voltage for 1 minute 32 42 55 65 95
Pulse-resistant voltage (kVp) 60 75 125 125 170
Cutting power (MVA) 100 100 200 200 250
Rated asynchronous short circuit (kAm.s) 5 5 12 12 16
Maximum environmental temperature (0C) 45 45 45 45 45
Maximum relative humidity (%) 98 98 98 98 98
Minimum detection line length (mm/kV) 20 20 20 20 20
Weight (kg) 7 7 8,2 8,7 13,5